Description
Model No. | NCA1C-500A/SP5 |
Production Capacity | 10000 Unit/Units per Month |
Usage | Magnetic Sensor |
Output | Current |
Brand Name | CSR |
Theory | Current Sensor |
Primary nominal | 500A rms |
2. Storage temperature: -40 C ~+80 C
3. Weight: approx. 60g
4. Standards: EN50178
Applications:
For the electronic measurement of currents: DC, AC, pulsed, mixed, with a galvanic isolation betwe
the primary circuit (high power) and the secondary circuit (electronic circuit).
Main technical data:
1. Primary normal current IPN (r.m.s) Primary current measuring range IP Type
500A +/-900A NCA1C-500A/SP5
2. Supply voltage(+/-5%): +5V
3. Current consumption: 10mA+ Secondary output voltage /loading resistance
4. Isolation test: Between the primary circuit to the secondary circuit(+.-.M): 3kVrms/50Hz/1min
5. Normal output voltage @RL=10,000 ohm , TA=+25 C: 2.5V±0.5Ip/InpV
6. Loading resistance: more than 1000 ohm
Accuracy – Dynamic performance Data
1. Accuracy @ IPN, TA=+25 C: +/-2%
2. Non-linearity (0~ IPN): +/-1% (+25℃)(without offset)
3. Electrical offset voltage VOE, TA=+25 C : not more than 2.5V+/-10mV
4. Hysteresis offset voltage @ IP=0,
after an drift of 1x IPN: not more than +/-10mV
5. Thermal drift of VOE: not more than +/-1mV/oC(-10oC~+80oC)
6. Response time (@ 90% of IP): not more than 5us
7. di/dt accurately followed: better than 50A/us
8. Frequency bandwidth(-3dB): DC 0 .. 50kHz
General data:
1. Operating temperature: -10 C ~+80 C
2. Storage temperature: -40 C ~+80 C
3. Weight: approx. 60g
4. Standards: EN50178
Features:
1. Hall effect measuring principle
2. Galvanic isolation between primary and secondary circuit
3. Insulated plastic case made of white PPO recognized according to UL 94-V0
4. The whole current transducer comply with RoHS Directive completely
Dimension:
Connection:
Output Voltage – Primary Current: